About PLC output type selection and precautions in use

1 . introduction
PLC output types are relay and transistor types. The operating parameters of the two are quite different. Before use, they need to be differentiated to avoid misuse and cause product damage. This article briefly introduced the characteristics of the relay and transistor output and the precautions in use.

Relay and transistor output operating principle

A relay is an electronic control device. It has a control system (also called an input circuit) and a controlled system (also called an output circuit). It is usually used in an automatic control circuit. It actually uses a smaller current to control a larger one. A "automatic switch" of current. Electromagnetic relays generally consist of iron cores, coils, armature, and contact reeds (as shown in Figure 1). As long as a certain voltage is applied to both ends of the coil, a certain current will flow through the coil to generate an electromagnetic effect, and the armature will absorb the pulling force of the return spring to the core under the action of the electromagnetic force to attract the armature. The movable contact and the stationary contact (normally open contact) are attracted. When the coil is de-energized, the electromagnetic suction force also disappears, and the armature returns to its original position at the reaction force of the spring, causing the movable contact to pull in contact with the original stationary contact (normally closed contact). This sucks and releases so as to achieve the purpose of turning on and off in the circuit. From the working principle of the relay, it can be seen that it is an electromechanical element. It is a contact element that achieves the on-off of contacts through mechanical actions.


Figure 1 electromagnetic relay structure


A transistor is an electronic component that controls the collector and emitter conduction through a base current. It is a contactless element.

The main difference between relay and transistor output

Due to the different working principle of the relay and the transistor, there is a big difference in the operating parameters of the two. The Emerson EC series PLC related data is used as an example for comparison and description (see the main specifications of the output port in Table 1).
(1) for driving a load can be connected to a different type of relay <br> 220V AC or 24V DC load requires no polarity; type transistor connected only 24V DC load, polarity requirements.
The load current of the relay can reach 2A, and the load current of the transistor is 0.2-0.3A. At the same time with the type of load, see Table 1 for details.

project

Relay output port

Transistor output port

External power supply

250Vac, 30Vdc or less

5-24Vdc

Circuit insulation

Relay mechanical insulation

Optocoupler insulation

Action instructions

Relay output contact closure indicator is lit

The indicator lights up when the optocoupler is driven

Leakage current at open circuit

/

Less than 0.1mA/30Vdc

Minimum load

2mA/5Vdc

5mA (5-24Vdc)

Maximum output current

Resistive load

2A/1 points;
8A/4 point group public end;
8A/8 point common

Y0, Y1: 0.3A/1 point Others: 0.3A/1 point
0.8A/4 points
1.2A/6 points
1.6A/8 point
Increases the total current by 0.1A for each additional point above 8 o'clock

Inductive load

220Vac, 80VA

Y0, Y1: 7.2W/24Vdc
Others: 12W/24Vdc

Light load

220Vac, 100W

Y0, Y1: 0.9W/24Vdc
Others: 1.5W/24Vdc

Response time

ON-OFF

Up to 20ms

Y0, Y1: 10us
Others: 0.5ms

OFF-ON

Up to 20ms

Y0, Y1 highest output frequency

/

100kHz per channel

Output common

Y0-COM0; Y1-COM1; After Y2 Up to every 8 ports use 1 common port, each common port is isolated from each other

Fuse protection

no

Table 1 Output port specifications
(2) the response time of the relay <br> different response times slower (about 10ms-20ms), the transistor is relatively fast response time of about 0.2ms-0.5ms, Y0, Y1 even up to 10 us.
(3) Since the service life of the relay is different <br> mechanical element is subjected life limits the frequency of operation, and is related to the load capacity as shown in Table 2, it can be seen from the table, with the increase in the load capacity of the contact life is almost Decrease by level. Transistors are only aging electronic components, no life-limits.

Load capacity

Action frequency condition

Contact life

220VAC, 15VA

1 second ON/1 second OFF

3.2 million times

220VAC, 30VA

1 second ON/1 second OFF

1.2 million times

220VAC, 60VA

1 second ON/1 second OFF

300 thousand times

Table 2 Relay life
4 . Relay and transistor output selection principle <br>Relay-type output drive current, slow response, mechanical life, suitable for driving intermediate relays, contactor coils, lights and other operating frequency is not high occasions. Transistor output drive current is small, high frequency, long life, suitable for controlling servo controllers, solid state relays and other applications requiring high frequency and long life. In high frequency applications, if you need to drive a large load at the same time, you can add other devices (such as relays, solid state relays, etc.) to drive.

Driving inductive load effects


Figure 2 Instantaneous high voltage generated when driving an inductive load

Relays control the opening and closing moments of inductive loads such as contactors. Since the inductor has a non-disruptive current characteristic, an instantaneous spike voltage will be generated between the two contacts of the relay according to U=L*(dI/dt). The voltage amplitude exceeds the derating of the contact resistance of the relay; the electromagnetic relay used in the relay, the withstand voltage between the contacts is 1000V (1min), if the voltage between the contacts works long-term around 1000V, It is easy to cause the migration and oxidation of the contact metal, resulting in the phenomenon of large contact resistance, poor contact, and contact adhesion. And the faster the operating frequency, the more serious the phenomenon. The transient high pressure is shown in Figure 2 below. The duration is within 1ms and the amplitude is above 1KV. This problem also exists when the transistor output is an inductive load. This transient high voltage can cause transistor damage.
Therefore, when the inductive load is driven, the absorption protection circuit should be connected to both ends of the load. When driving inductive loads (such as relay coils) of the DC circuit, the user circuit must be connected in parallel with a freewheeling diode (requiring attention to the polarity of the diode); if the inductive load of the AC circuit is driven, the user circuit needs to connect the RC surge absorbing circuit in parallel to protect PLC output contacts. PLC output contact protection circuit shown in Figure 3.


Figure 3 PLC output contact protection circuit

Matters needing attention in use

A common feature of the customer's site where relay problems often occur on the market today is that the faulty output point has a faster operating frequency, and the driven loads are inductive loads such as relays, solenoid valves or contactors, and do not absorb the protection circuit. Therefore, it is recommended that the following points should be noted when selecting and using PLC output types:

Must pay attention to the load capacity . The output port must comply with the maximum allowable current limit (as shown in Table 1) to ensure that the heat output of the output port is limited to the allowable range. The service life of the relay is related to the load capacity. When the load capacity increases, the contact life will be greatly reduced (as shown in Table 2), so pay special attention. Must pay attention to the nature of the load . According to the analysis in Section 4, inductive load will generate instantaneous high pressure at the instant of opening and closing, so the apparent load capacity may not be large on the surface, but actually the load capacity is large, and the life of the relay will be greatly shortened, so when driving inductive load, The absorption protection circuit should be inserted at both ends of the load. Especially when the operating frequency is relatively high, be sure to increase the protection circuit. From the perspective of customers' usage, the effect of improving the absorption and protection circuit is very obvious.

According to the characteristics of the capacitor, if the capacitive load is directly driven, an inrush current will be generated at the moment of conduction. Therefore, in principle, the output port should not be connected to a capacitive load. If necessary, ensure that the surge surge current is smaller than the specification (see table 1) The maximum current in the description.

Must pay attention to the frequency of action . When the operating frequency is high, it is recommended to select the transistor output type. If a large current is to be driven at the same time, the transistor output can be used to drive the intermediate relay mode. When controlling a stepper motor/servo system, or using a high-speed output/PWM wave, or a node with a high operating frequency, only the transistor type can be used. PLC does not require the same output type between the expansion module and the main module. Therefore, when there are many system points and different functions, you can consider the relay output main transistor extension transistor output or the transistor output main module extension relay output to achieve the best match .

Facts have proved that according to the correct selection of the type and capacity of the load and the frequency of operation and system design, the failure rate of the output port has decreased significantly, and the customer is very satisfied.

references:
Emerson EC20 Series Programmable Controller User Manual

Leisuwash specializing in manufacture Automatic Car Wash Machine, Touchless Car Wash , Automatic Touchless Car Wash, touchless car wash equipment, robot car wash, smart car wash system, leisuwash 360, leisuwash leibao 360, laserwash 360, leisuwash touchless car wash machine, leisu wash touchless car wash automatic, leisu wash 360 high pressure touchless car wash equipment, robo car wash, touch free car wash, leisuwash 360 touch free car wash, leisuwash 360 price, automatic car wash price, leisuwash in malaysia, no touch automatic car wash machine.
Leisuwash 360 touchless car wash machine high intelligent high quality, with car wash + car care + drying process totally, each car wash takes time 1 minute to 5 minutes which depends on the car wash mode.
Automatic Touch Free Car Wash Equipment more and more popular in car wash business market, as can save employee fees and wash time mostly, bring investor much more benefit profit return. That's why choose the automatic car washing system.

Touch Free Car Wash Equipment

Touch Free Car Wash Equipment,Automatic Car Wash,Leisuwash Touchless Car Wash,Automatic Car Wash Machine

Hangzhou Leisu Cleaning Equipment Co.,Ltd , https://www.sdtouchfreecarwash.com